Fire and Building Inspector Training IFC Quiz 23


Home Next Quiz

221) You are inspecting a new 505 square foot portable boiler that produces 500,000 BTU/hour output that just arrived on site. It has one exit door. People are moving in. What is your finding?

Hint2015 IFC Section 1006.2.2.1

222) A sprinklered business (Group-B) occupancy building has a room that is 75’X80’. It has one exit access door in the center of one of the walls. Is this a problem?

Hint2015 IFC Table 1004.1.2, Table 1006.2.1

223) A sprinklered business occupancy has a single door midway on a 50’ wall. The overall footprint of the building is 40’X100’. Is there a problem?

Hint2015 IFC Table 1004.1.2, Table 1006.2.1

224) A sprinklered open warehouse with a footprint of 100’X100’ has only one door midway on one of the walls. Is this a problem?

Hint2015 IFC Table 1004.1.2, Table 1006.2.1, Warehouse is Group-S [100X100/500 = 20, (100^2+50^2)^.5 < 125]

225) A 3-story business occupancy with two exits has been retrofitted for an assembly type occupancy where the occupancy load has gone up to 600 personnel on the 2nd floor. The first floor doors were not updated. Is this a problem?

Hint2015 IFC Table 1006.3.1)

226) The business side of a sprinklered mixed use 30,000 ft2 business and industrial occupancy has been remodeled. It requires two doors based upon occupancy and common path of travel. The two doors have been placed on the east facing side. All the other exit doors have been removed, even the ones into the adjacent industrial area. The diagonal distance of the building from corner to corner is 128’. The doors are placed 40’ apart. Is this a problem?

Hint2015 IFC Section 1007.1.1 Exception 2

227) An occupant of a 1,500 ft2 room within a business occupancy comes to you complaining that there is a code violation because there is no exit sign or emergency lighting in this room. There is only one exit access door from this sprinklered room. What do you tell this person?

Hint2015 IFC Section 1008.3.1, 1013.1 Exception 1, Table 1006.2.1, Table 1004.1.2

228) The electricians come to you asking how long to perform an acceptance test of light operation for newly installed emergency lighting. What do you tell them?

Hint2015 IFC Section 1008.3.4

229) The safety group comes to you with a report that a corridor served by an emergency light was tested at only 2 foot-candles when the power went off. They want to add another emergency light. What do you tell them?

Hint2015 IFC Section 1008.3.5

230) What is the minimum CLEAR width of any new door?

Hint2015 IFC Section 1010.1.1